Cooper Bussmann, LPJ-350SP, Dual Element Time Delay Fuse, Class J

Cooper Bussmann, LPJ-350SP, Dual Element Time Delay Fuse, Class J

Dual Element Time Delay Fuse, Class J, 350A, 300kA @ 600VAC / 100kA @ 300VDC Interrupt Rating, 2.11"x7.13"

SKUM37367
ManufacturerCooper Bussmann
Mfr. Part #LPJ-350SP
UPC051712522830
Points2.58
$257.59
   
Features
  • Application : Power Panelboards / Branch Circuit Breaker Panelboard Mains / Machinery Disconnects / Industrial Control
  • Separate overload and short-circuit elements provide time delay for sizing of high inrush loads linked with Class J current limitation
  • Selective coordination ratio of 2:1 (within Low-Peak fuse family) prevents electrical shutdowns from extending beyond the failed circuit
  • Series combination ratings with branch circuit breakers allows broad range of coverage, independent of breaker manufacturer
Downloads
Specification
Type Dual-Element, Time-Delay Fuse; 10 Seconds (Minimum) at 500% Rated Amps
Class Class J
Maximum AC Voltage (V AC) 600
Maximum DC Voltage (V DC) 300
Amperage Rating (A) 350
Interrupting Ratings @ 600VAC k(A) 300
Interrupting Ratings @ 300VDC (kA) 100
Construction Copper fuse element
Dia (In.) 2.11
Length (In.) 7.13
Standard CE, UL Listed - Special Purpose, Guide JFHR, File E56412, CSA Certified (200,000 AIR) Class J per CSA-22.2 No. 248.8, Class 1422-02, File 53787